BACHARACH MVR-SC Controller
BACHARACH MVR-SC Controller Fixed Gas Leak Detector  Selangor, Malaysia, Kuala Lumpur (KL), Shah Alam Supplier, Suppliers, Supply, Supplies | Precizion Tools System Settings Alarm Detected Page
Quantity
Download Files
mvrSC-MKTG00151-en-0.pdf (1.61 MB)
Centralized Controller for Refrigerant Leak Detection
  • Centralized monitoring for multi-occupant applications utilizing the MVR-300™ VRF Refrigerant Gas Detector
  • At-a-glance visualization of whole system alarm, fault, or connectivity status
  • Continuously monitors up to 100 connected devices for alarm and fault conditions, ensuring and warning in case of any disconnect
  • Rolling event log of 100 most recent events (alarms, faults, connectivity, etc.) saved to SD card
  • 1 Alarm Relay; 1 Fault Relay; automatic system action to be taken for fault or alarm condition via built-in relays
  • Self diagnostics and simple field calibration for easy maintenance
  • Commissioning via dynamic device pairing and remote Modbus auto-assign save


The MVR-SC Refrigerant Leak Monitor provides centralized monitoring and alarming for multi-occupant applications utilizing the MVR-300™ VRF Refrigerant Leak Detector. The MVR-SC continuously monitors all connected gas detectors for alarm and fault conditions, and will provide alerts via the integrated color touchscreen display, integrated buzzer, and on-board relay outputs.

IMPORTANT NOTE: Large refrigerant leaks into occupied spaces can reach concentrations that pose a suffocation risk to the occupants. The MVR-300™ is not designed to be used as the sole safety device for this risk. Safety of the occupants also must take a system designed approach that includes things such as ventilation, detection, early warning, mitigation and design redundancy.


Specifications

Housing Fiberglass Reinforced Polyester, Wall Mount, Single-door
Dimensions 13.56 × 11.43 × 5.46 inches (344 × 291 × 139 mm)
Weight 7.8 lb (3.54 kg)
Display Type Color Touch Display, Resistive Analog, TFT
Display Viewing Size 5 inch, 800 × 480 pixels
Audible Alarm Integrated
Relay Outputs 2 (Fault, Alarm)
Relay Output Type Fault and Alarm
Relay Switching Rating 2.0 Amps switching current, max 250VAC / 30 VDC
Max. Devices 100 × MVR-300 VRF refrigerant leak detectors
15 × MVR-300 VRF refrigerant leak detectors / Gateway
7 × Gateways / MVR-SC refrigerant leak monitor
Communication Modbus TCP Master, 10/100 Ethernet, RJ45 Port
Serial Port 1 × RS485 Modbus RTU Master (for direct addressing)
Memory Storage microSD Card and USB 2.0
Backup Battery CR2032 (Real-time Clock)
Operating Voltage 24V DC
Input Voltage Range 20.4VDC to 28.8VDC
Max. Current Consumption 0.44A @ 24VDC
Operating Temperature -20º C to 55º C (-4º F to 131º F)
Storage Temperature -30º C to 70º C (-22º F to 158º F)
Relative Humidity 5% to 95%
Approvals (Pending) EN 61326-1:2013